RNG-320D V1.4: 320 W rigid mono panel, Vmp 32.7 V, Voc 40.1 V and Isc 10.36 A. 1665 × 1002 × 35 mm, 18 kg; use suitable MPPT and cold-voltage margin for a 12 V bank.
- Nominal voltage
- 32.7 V
- Rated power
- 320 W
- Rated output
- 9.8 A
Wiring diagram
How the 320W Mono is wired.
Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.
Cable sizing for this example
Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.
3 m one way
32.7 V panel Vmp
- Wire
- 1.5 mm² · 16 AWG
- Example fuse
- 15 A
- Design current
- 9.8 A
- Voltage drop
- 2.1%
Sized against ABYC E-11. The design current is the part's continuous draw. The length is one way; voltage drop includes an equal-length return.
Run-length and manufacturer assumptions
The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.
Supporting parts
- 6.1 m total of 1.5 mm² (16 AWG) marine cable
- Terminations for 1.5 mm² cable, matched to the equipment's screw terminals, leads or studs
- 15 A fuse and holder on the positive run
- Heat-shrink, strain relief and terminal boots sized to the cable
Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.
Installation notes
Before you install.
Open a question for model-specific guidance and sources.
Verified against the manufacturer's documentation (rev. V1.4), checked 2026-10-01. Manufacturer documentation →
Match RNG-320D revision V1.4
Renogy's V1.4 RNG-320D sheet describes a 320 W, 60-cell rigid monocrystalline panel. Its exact-model table gives 32.7 V Vmp, 9.79 A Imp, 40.10 V Voc and 10.36 A Isc. The catalog has been aligned with that edition, correcting the previous 33.7 V / 9.5 A operating point. Check an older panel's label before assuming every production revision is identical. See datasheet, page 2.
The same sheet specifies 1665 × 1002 × 35 mm and 18 kg. Those are physical panel dimensions, unrelated to the canvas symbol size.
Connect a controller and check the string voltage
This is a higher-voltage panel even when used in a nominal 12 V installation. Connect it through an MPPT controller suitable for the battery and array. The controller must accept the complete string's cold-weather open-circuit voltage, not merely the 32.7 V working voltage.
The verified Voc temperature coefficient is −0.30%/°C. Cold cells increase the 40.10 V STC value. Add panel voltages for series strings; for parallel strings add the currents and assess possible reverse current into a faulted string. The module's 1000 V maximum system voltage does not override the controller's lower rating.
Select protection and extensions from the actual hardware
The maximum series-fuse rating is 15 A. It is a ceiling for module protection, not a universal instruction to install a 15 A fuse. Determine whether string fuses are needed from the array arrangement and size them with the cable, controller and installation requirements.
The panel has 12 AWG, approximately 3 ft output leads, a junction box with two bypass diodes and locking solar connectors. The separate 30 A connector rating does not increase the 15 A module-fuse ceiling. Match extension connectors to the actual fitted manufacturer/type, support their weight, and keep mating surfaces clean and dry.
Mount and commission the array
Use the intended frame mounting locations, preserve drainage and ventilation, and select a support suitable for the roof and wind loads. Do not lift the panel by its leads or unplug connectors under load. Renogy's family installation manual, sections 2.1.2 and 2.2.3, covers mounting and system connection.
Follow the controller's sequence; the Renogy example connects and configures the battery before connecting PV. Verify polarity and open-circuit voltage before energizing, then check charging under sunlight. The 320 W rating is an STC rating, not a guaranteed battery-side output in every season or mounting position.
Technical reference
Specifications and terminal map.
Check the model, ratings and connection points against your own unit before choosing installation hardware.
Catalog specification
RNG-320D V1.4: 320 W rigid mono panel, Vmp 32.7 V, Voc 40.1 V and Isc 10.36 A. 1665 × 1002 × 35 mm, 18 kg; use suitable MPPT and cold-voltage margin for a 12 V bank.
- Nominal voltage
- 32.7 V
- Rated power
- 320 W
- Rated output
- 9.8 A
- Panel open-circuit voltage
- 40.1 V
Terminal map
Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.
+
positive · bidi
−
negative · bidi
Sources and sizing method
Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.
Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.
Read how the sizing worksNext step
Plan your installation with 320W Mono.
Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.