RNG-175DB-H

Renogy 175W Flexible wiring diagram

Legacy RNG-175DB-H: 175 W flexible mono, 1504 × 673 × 2 mm, 2.8 kg. Voc 24.9 V and 20 A maximum series fuse; current G2 electrical values differ. Installed bend and adhesive method require the mounting instructions.

Nominal voltage
20.3 V
Rated power
175 W
Rated output
8.8 A

Wiring diagram

How the 175W Flex is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Renogy 175W Flexible wiring example with 3 components: 175W Flex, Solar controller, House bank. 4 cable connections. Crossings are not junctions.175W Flex + to Solar controller PV +: 2.5 mm² · 15 A fuse, 3 m one way. 175W Flex − to Solar controller PV −: 2.5 mm², 3 m one way. Solar controller BATT + to House bank +: 10 mm² · 25 A fuse, 3 m one way. Solar controller BATT − to House bank −: 10 mm², 3 m one way175W Flex + to Solar controller PV +: 2.5 mm² · 15 A fuse, 3 m one way175W Flex − to Solar controller PV −: 2.5 mm², 3 m one waySolar controller BATT + to House bank +: 10 mm² · 25 A fuse, 3 m one waySolar controller BATT − to House bank −: 10 mm², 3 m one wayRenogy 175W Flexible175W Flex++−−Victron MPPT 100/20. Single-panel, 12 V charging example. Check the actual panel's cold-weather open-circuit voltage, short-circuit current and the controller limits before adapting it.Solar controllerPV +PV +PV −PV −BATT +BATT +BATT −BATT −12 V 200 Ah house bankHouse bank++−−2.5 mm² · 15 A fuse2.5 mm²10 mm² · 25 A fuse10 mm²
Renogy 175W Flexible wiring example with 3 components: 175W Flex, Solar controller, House bank. 4 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Wire sizes and fuse ratings are example values; use the equipment instructions and actual installation lengths.
Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

3 m one way

20.3 V panel Vmp

Wire
2.5 mm² · 13 AWG
Example fuse
15 A
Design current
8.8 A
Voltage drop
1.8%

Sized against ABYC E-11. The design current is the part's continuous draw. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

Show sizes in AWG

Supporting parts

  1. 6.1 m total of 2.5 mm² (13 AWG) marine cable
  2. Terminations for 2.5 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 15 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. Undated manufacturer datasheet; accessed 2026-10-01), checked 2026-10-01. Manufacturer documentation →

Identify the flexible panel revision

The RNG-175DB-H sheet specifies 175 W, 20.3 V Vmp, 8.75 A Imp, 24.9 V Voc and 9.65 A Isc at standard test conditions. This is the original electrical version, documented in a Renogy-authored sheet archived by NaradiHned. A newer G2 download retains the model name but changes voltage, current and fuse limits; its values are not used here. See exact-model datasheet, page 2.

The frameless panel measures 1504 × 673 × 2 mm and weighs 2.8 kg. Its thin laminate needs a supported installation; flexibility is not permission to crease it or use it as a loose roof covering.

Wire the controller and extensions

Connect the marked positive and negative leads through a solar charge controller, never directly to a house battery. The sheet gives 12 AWG leads, 150 mm positive and 450 mm negative. Match locking extension connectors to the fitted hardware and route cables without pulling on the junction box. Keep connectors accessible for inspection and isolate the circuit before disconnecting them.

Series connection adds voltage; parallel connection adds current. Check both against the controller, wiring and protection design. For a 12 V battery, confirm the controller can operate with this panel's hot-weather working voltage and cold-weather open-circuit voltage.

Check cold voltage and reverse-current protection

The exact sheet gives −0.31%/°C Voc temperature coefficient, 600 V maximum module-system voltage, and 20 A maximum series fuse rating. Calculate the complete string's cold Voc from the actual lowest design temperature and required margins. The module-system rating does not establish a controller input limit.

The fuse figure is the module's protection ceiling, not a mandatory fuse size for every layout. Assess parallel-string reverse current and cable capacity. Crimp's terminal-current planning value and the connector's separate rating are not substitutes for that calculation.

Preserve drainage, cooling and the installed bend limit

Renogy's current family installation manual, section 2.1.3, printed page 55, calls for a compatible structural adhesive method, open short edges for drainage/heat escape, 5–10 mm between panels, and 72 hours curing protection. For corrugated roofs it requires at least six adhesive contact lines; otherwise this mounting method is unsuitable.

The same guidance limits the actual installed bend angle to 30°. A much larger advertised handling bend is not an installed-roof design limit. Confirm adhesive compatibility with the roof and actual panel revision before bonding, provide ventilation, and keep walking loads and sharp edges away from the laminate. Set battery charging parameters before connecting PV, then inspect attachment and output after commissioning.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Legacy RNG-175DB-H: 175 W flexible mono, 1504 × 673 × 2 mm, 2.8 kg. Voc 24.9 V and 20 A maximum series fuse; current G2 electrical values differ. Installed bend and adhesive method require the mounting instructions.

Nominal voltage
20.3 V
Rated power
175 W
Rated output
8.8 A
Panel open-circuit voltage
24.9 V

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

+

positive · bidi

15 A

−

negative · bidi

15 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with 175W Flex.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Start drawing, sizing and checking without an account. Your drawing saves in this browser. See Pricing for the equipment allowance and the one-time export offer available to you.