Lithium NG 25.6V/200Ah

Victron Lithium NG 25.6V 200Ah wiring diagram

Plan the Victron Lithium NG 25.6V 200Ah DC power path with its required smallBMS NG and a BatteryProtect load disconnect. Complete the battery data and shutdown controls from the manufacturer diagram before installation.

Nominal voltage
25.6 V
Capacity
200 Ah
Maximum discharge
200 A

Wiring diagram

DC power path for the Lithium NG 25.6/200.

The drawing includes the required battery-management and load-disconnect hardware. Battery data and shutdown control leads are not represented by these symbols; use the complete manufacturer instructions to connect and test them.

Victron Lithium NG 25.6V 200Ah wiring example with 6 components: Lithium NG 25.6/200, ATC inline fuse holder, smallBMS NG, BMS-controlled load disconnect, Fused DC distribution, DC fridge. 9 cable connections. Crossings are not junctions.Lithium NG 25.6/200 + to BMS-controlled load disconnect IN: 6 mm², 50 cm one way. Lithium NG 25.6/200 + to ATC inline fuse holder IN: 1.5 mm², 10 cm one way. ATC inline fuse holder OUT to smallBMS NG +: 1.5 mm² · 1 A fuse, 30 cm one way. Lithium NG 25.6/200 − to smallBMS NG −: 1.5 mm², 50 cm one way. BMS-controlled load disconnect OUT to Fused DC distribution IN +: 6 mm² · 7.5 A fuse, 50 cm one way. Lithium NG 25.6/200 − to Fused DC distribution IN −: 6 mm², 1 m one way. Lithium NG 25.6/200 − to BMS-controlled load disconnect GND: 0.3 A sense fuse, 50 cm one way. Fused DC distribution 1 to DC fridge +: 6 mm² · 7.5 A fuse, 1 m one way. Fused DC distribution 1 to DC fridge −: 6 mm², 1 m one wayLithium NG 25.6/200 + to BMS-controlled load disconnect IN: 6 mm², 50 cm one wayLithium NG 25.6/200 + to ATC inline fuse holder IN: 1.5 mm², 10 cm one wayATC inline fuse holder OUT to smallBMS NG +: 1.5 mm² · 1 A fuse, 30 cm one wayLithium NG 25.6/200 − to smallBMS NG −: 1.5 mm², 50 cm one wayBMS-controlled load disconnect OUT to Fused DC distribution IN +: 6 mm² · 7.5 A fuse, 50 cm one wayLithium NG 25.6/200 − to Fused DC distribution IN −: 6 mm², 1 m one wayLithium NG 25.6/200 − to BMS-controlled load disconnect GND: 0.3 A sense fuse, 50 cm one wayFused DC distribution 1 to DC fridge +: 6 mm² · 7.5 A fuse, 1 m one wayFused DC distribution 1 to DC fridge −: 6 mm², 1 m one wayVictron Lithium NG 25.6V 200Ah. 30 A MRBF is an illustrative source fuse for this small fridge circuit, not a battery maximum-current recommendation. Verify the fuse's interrupt capacity and terminal hardware for this battery. 24 V DC power paths with smallBMS NG and a BatteryProtect load disconnect. Connect the required NG M8 battery chain, remote-enable loop and Load disconnect-to-BatteryProtect control before use; those terminals are absent from the symbols. Add charge-stop controls for any charger. BMS shutdown operation is not verified by the drawing.Lithium NG 25.6/20030 A MRBF at battery +++−−ATC inline fuse holder. Illustrative inline holder, 0.1 m from battery. Verify the installed holder, fuse voltage and interrupt rating.ATC inline fuse holder1 AINOUTVictron smallBMS NG. Connect the matching NG battery M8 chain and remote-enable loop. Connect Load disconnect to the BatteryProtect REMOTE input; configure lithium mode. The 1 A supply fuse is within the manual's 0.3–2.5 A range for this control-only example. Control and battery-data terminals are not represented by these catalog symbols.smallBMS NG+−−Victron BatteryProtect 100. BatteryProtect IN is battery-side and OUT supplies the loads. Connect the REMOTE input to smallBMS NG Load disconnect. Configure lithium mode. The GND reference has the manual's separate 300 mA fuse and 1.5 mm² conductor; never use it as a load return. Remote-control terminals are not drawn.BMS-controlled loaddisconnectINOUTGNDGNDBlue Sea 5025 ST Blade Fuse BlockFused DC distributionIN +IN +IN −IN −1111Dometic CRX-65 Fridge. This 12 V example uses Dometic's 15 A supply protection and a short 1 m run with 6 mm² cable. Check the manual's voltage-specific cable graph for your route. At 24 V, the specified protection is 7.5 A. Running current and the fuse rating describe different things.DC fridge++−−6 mm²1.5 mm²6 mm²
Victron Lithium NG 25.6V 200Ah wiring example with 6 components: Lithium NG 25.6/200, ATC inline fuse holder, smallBMS NG, BMS-controlled load disconnect, Fused DC distribution, DC fridge. 9 cable connections. Crossings are not junctions.24 V DC power paths with smallBMS NG and a BatteryProtect load disconnect. Connect the required NG M8 battery chain, remote-enable loop and Load disconnect-to-BatteryProtect control before use; those terminals are absent from the symbols. Add charge-stop controls for any charger. BMS shutdown operation is not verified by the drawing. Red = positive · dark = return · dashed = signal. Wire sizes and fuse ratings are example values; use the equipment instructions and actual installation lengths.
Edit this DC power path

DC power-path sizing

The example supplies a small fridge circuit through compatible battery management and load-disconnect hardware. Its power paths do not verify the required BMS communication, remote control or shutdown behavior.

Cable sizes depend on the connected equipment, current and cable lengths. Add those details in Crimp to size each run.

View diagram in AWG

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. 11 — 03/2026), checked 2026-10-01. Manufacturer documentation →

Identify the NG generation

This is the Lithium NG 25.6 V/200 Ah, a 5.12 kWh battery for a nominal 24 V system. It requires a compatible Victron NG BMS. The March 2026 manual describes smallBMS NG, Lynx Smart BMS NG and VE.Bus BMS NG options; choose according to how the system must disconnect loads and chargers. The older Lithium Battery Smart BMS family is not interchangeable. See BMS selection, printed pages 4–8.

Connect the battery data loop

The battery communicates through its M8 male/female BMS leads. Daisy-chain those leads through the bank and connect the first and last to the BMS. These are separate from the power terminals and are not a direct BMS-Can connection. A Lynx Smart BMS NG can communicate onward with a GX device through VE.Can; Bluetooth monitoring also resides in the BMS. See BMS connections, printed page 15.

Apply temperature-dependent current limits

The specification permits 200 A continuous charge/discharge and 400 A for ten seconds for this model. Crimp uses the continuous values; its 500 A terminal planning allowance is not a battery or stud rating. Victron recommends 0.5C charging, or 100 A here.

Charging is permitted at +5 to +50°C, with current reduced to 0.3C, or 60 A, below 15°C. Discharge is permitted at −20 to +50°C, reducing to 0.5C, or 100 A, at or below 0°C. Both need further derating above 35°C according to the manual's curves. See operating conditions, printed pages 20–21.

Mount, fuse and expand the bank

Use M8 power terminals at 10 Nm, lugs against the terminal and washers above. Install dry and indoors, with 20 mm clearance on four sides; upright or side mounting is allowed, terminals downward is not. Fuse the positive connection according to the lowest applicable cable, battery and system limit.

At most two 25.6 V batteries go in series. The manual allows 50 batteries total per BMS, with individual parallel batteries or series strings fused and balanced current paths. Fully charge and balance each before series connection; do not connect loads or links to string midpoints. See installation, printed pages 13–15.

Verify shutdown before service

For manually configured chargers, use 28.4 V absorption for two hours, 27.0 V float, with temperature compensation disabled. Supported DVCC-controlled equipment receives settings automatically. Commission the system by checking that disconnecting a BMS lead stops all chargers and loads, then verify recovery after reconnection. See settings and commissioning, printed page 16.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Lithium NG 25.6V 200Ah battery requiring a compatible external NG BMS and M8 BMS data leads. 200A continuous charge/discharge, with temperature derating; not compatible with older Smart-family BMS units.

Nominal voltage
25.6 V
Capacity
200 Ah
Maximum discharge
200 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

+

positive · bidi

500 A

−

negative · bidi

500 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Wire sizes and fuse ratings apply to the connected example, not a fixed cable size for this component. Set your actual equipment, current, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with Lithium NG 25.6/200.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Start drawing, sizing and checking without an account. Your drawing saves in this browser. See Pricing for the equipment allowance and the one-time export offer available to you.