Phoenix 12/800 VE.Direct

Victron Phoenix Inverter 12/800 wiring diagram

Legacy Phoenix 12/800 VE.Direct: 650 W at 25°C / 560 W at 40°C, 12 V DC input. Class I chassis protective earth is required. Confirm the AC socket/voltage version and neutral-bond arrangement; newer HW15 ratings do not apply.

Compatible systems
12 V
Rated power
650 W
Continuous draw
60 A

Wiring diagram

How the Phoenix 800 is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Victron Phoenix Inverter 12/800 wiring example with 3 components: House bank, Battery disconnect, Phoenix 800. 3 cable connections. Crossings are not junctions.Battery disconnect B to Phoenix 800 DC +: 25 mm² · 100 A fuse, 3 m one way. House bank − to Phoenix 800 DC −: 25 mm², 3 m one way. House bank + to Battery disconnect A: 25 mm² · 100 A fuse, 30 cm one wayBattery disconnect B to Phoenix 800 DC +: 25 mm² · 100 A fuse, 3 m one wayHouse bank − to Phoenix 800 DC −: 25 mm², 3 m one wayHouse bank + to Battery disconnect A: 25 mm² · 100 A fuse, 30 cm one way12 V 200 Ah house bankHouse bank++−−Main Battery SwitchBattery disconnectABVictron Phoenix Inverter 12/800Phoenix 800DC +DC +DC −DC −25 mm² · 100 A fuse25 mm²25 mm² · 100 A fuse
Victron Phoenix Inverter 12/800 wiring example with 3 components: House bank, Battery disconnect, Phoenix 800. 3 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Wire sizes and fuse ratings are example values; use the equipment instructions and actual installation lengths.
Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

3 m one way

12 V system

Wire
25 mm² · 4 AWG
Example fuse
100 A
Design current
60 A
Voltage drop
2.1%

Sized against ABYC E-11. The design current is the part's continuous draw. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

Show sizes in AWG

Supporting parts

  1. 6.1 m total of 25 mm² (4 AWG) marine cable
  2. Terminations for 25 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 100 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Reviewed against manufacturer family documentation (rev. Version 01 — July 16th, 2024), checked 2026-10-01. Exact variant details still require confirmation. Manufacturer documentation →

Which Phoenix generation is covered?

These notes cover the legacy Phoenix/Inverter 12/800 VE.Direct described in Victron's July 2024 manual. Its model specification table rates 800 VA, with 650 W continuous at 25°C, 560 W at 40°C, and 1500 W peak. The catalog's continuous rating therefore matches this older generation. Newer HW15 products have different power ratings; do not transfer their figures or terminal torques to this unit without matching the part number.

The 12/ prefix means nominal 12 V DC input. AC versions have different sockets and nameplates; confirm whether the installed inverter supplies 230 V or 120 V. The generic catalog record does not identify a complete hardware/AC suffix, so this remains family-qualified.

What connections are represented?

DC + / DC − are the battery input. AC L / AC N represent the output socket conductors, not a shore-power input. The Chassis PE port represents the required external Class I protective-earth lug. Preserve the output socket's earth connection as well. Its 125 A catalog limit is a planning envelope copied from the existing DC terminals, not a manufacturer earth-lug ampacity. The remote on/off connector and VE.Direct port remain omitted.

Appendix B specifies an earth conductor at least half the battery-cable cross-section, using its tabulated conductor sizes; the earth lug accepts at most 25 mm². This protective conductor is separate from the normal DC return.

Neutral-to-earth bonding depends on the outlet version and installation. The manual says standard units have an isolated/floating output, while GFCI versions are bonded internally. Have that arrangement checked before relying on an RCD/GFCI; do not assume the drawn N is already earth-referenced. Never connect the inverter output directly to another energized AC source. A shore/inverter installation requires suitable transfer equipment.

What DC cable and protection are specified?

The battery table, printed page 4, gives 16 mm² for 0–1.5 m and 25 mm² for 1.5–3 m on the 12/800, with 100 Ah minimum battery capacity as its guideline. Actual battery discharge capability and BMS limits must also support startup demand. The model's terminal capacity is 25 mm²; this legacy manual establishes no numeric tightening torque.

The listed 150 A BF1 internal fuse is distinct from battery-cable protection. The manual requires an additional fuse/breaker near the battery for cables beyond 1.5 m, and for UL NEMA-GFCI versions at every cable length. Select battery-side protection with the installed conductor and applicable installation requirements; do not present the internal fuse as a universally specified external rating.

Which operating settings matter?

Configure low-voltage shutdown/restart and ECO mode through VE.Direct. Bluetooth requires the separate VE.Direct Bluetooth Smart dongle on this generation. Default ECO wake-up is 15 W, checked every 2.5 seconds; small electronics may fail to remain powered in ECO. Normal no-load consumption is about 6.5 W for the 12 V model, versus 1 W in default ECO.

Where should it be installed?

Use a dry, ventilated IP21 location with 100 mm clearance around the unit. Follow the mounting-orientation drawings and keep ventilation openings unobstructed. Check battery polarity before energizing, then test the intended load and shutdown behavior. Heat, cable voltage drop and motor starting surges can reduce usable capacity below the headline wattage.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Legacy Phoenix 12/800 VE.Direct: 650 W at 25°C / 560 W at 40°C, 12 V DC input. Class I chassis protective earth is required. Confirm the AC socket/voltage version and neutral-bond arrangement; newer HW15 ratings do not apply.

Compatible systems
12 V
Rated power
650 W
Continuous draw
60 A
Surge current
139 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

DC +

positive · input

125 A

DC −

negative · input

125 A

AC L

neutral · output

7 A

AC N

neutral · output

7 A

Chassis PE

ground · bidi

125 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with Phoenix 800.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Start drawing, sizing and checking without an account. Your drawing saves in this browser. See Pricing for the equipment allowance and the one-time export offer available to you.