Load
Lewmar V700 Windlass wiring diagram
12 V vertical windlass, 320 W motor. Lewmar issue 8 specifies 45 A normal current and a 35 A breaker, with 79 kg working-load limit and 320 kg maximum pull. Requires matched reversing controls and independent anchor restraint.
- Compatible systems
- 12 V
- Rated power
- 320 W
- Continuous draw
- 45 A
Wiring diagram
How the V700 windlass is wired.
Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.
Cable sizing for this example
Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.
3 m one way
12 V system
- Wire
- 16 mm² · 6 AWG
- Example fuse
- 60 A
- Design current
- 45 A
- Voltage drop
- 2.5%
Sized against ABYC E-11. The design current is the part's continuous draw. The length is one way; voltage drop includes an equal-length return.
Run-length and manufacturer assumptions
The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.
Supporting parts
- 6.1 m total of 16 mm² (6 AWG) marine cable
- Terminations for 16 mm² cable, matched to the equipment's screw terminals, leads or studs
- 60 A fuse and holder on the positive run
- Heat-shrink, strain relief and terminal boots sized to the cable
Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.
Installation notes
Before you install.
Open a question for model-specific guidance and sources.
Verified against the manufacturer's documentation (rev. 65001022 issue 8), checked 2026-10-01. Manufacturer documentation →
Read the 12 V V700 ratings separately
The V700 manual's specification table on page 4 lists a 320 W motor, 45 A normal current, a 35 A circuit breaker and a 79 kg working-load limit. Its 320 kg maximum pull is a different condition. The current and breaker figures are not interchangeable, and the motor's watt label is not a complete prediction of battery current under load.
Connect the complete reversing circuit
The canvas's positive and negative pins represent the supply to the windlass circuit. They do not replace the reversing controls. Page 8 shows the specified 0052519 toggle switch carrying motor current directly. Page 9 instead uses contactor 0052531 with a 3 A control fuse for the rocker, foot switches and handheld control. Match the fitted arrangement; small control switches must not replace the specified power-switching hardware. Both diagrams include the 35 A breaker/isolator 68000604.
Identify motor cable colours and the actual switch/contactor terminals before terminating cables. Test direction with the rode clear and a person watching the windlass, then isolate before adjustments.
Size the complete cable route
Section 5 sizes conductors by the full positive-and-negative route, including the switchgear. Measure both legs, evaluate loaded voltage at the motor and check the manufacturer's cable chart alongside installation ampacity requirements. A stalled or heavily loaded windlass draws more than its normal-current figure; do not enlarge the breaker to conceal poor battery voltage, corroded joints or a mechanical jam.
The catalog's surge and terminal limits are planning assumptions, not separately verified V700 motor or connector ratings. Confirm any design that depends on them with the installed unit's documentation.
Arrange the anchor handling hardware
Confirm the gypsy matches the actual chain standard and rope. Preserve the required chain fall and clearance below deck; a pile-up in the locker can look like an electrical failure. The manual also covers fall-safe operation and manual recovery. Secure the anchor and rode independently when under way or lying at anchor, rather than loading the windlass continuously.
Switch off the breaker/isolator when the windlass is not in use. Before service, isolate its electrical supply and secure the anchor; clear the mechanism before restoring power. Periodically inspect the rode, mounting, corrosion protection and cable connections as described in sections 7–9.
Technical reference
Specifications and terminal map.
Check the model, ratings and connection points against your own unit before choosing installation hardware.
Catalog specification
12 V vertical windlass, 320 W motor. Lewmar issue 8 specifies 45 A normal current and a 35 A breaker, with 79 kg working-load limit and 320 kg maximum pull. Requires matched reversing controls and independent anchor restraint.
- Compatible systems
- 12 V
- Rated power
- 320 W
- Continuous draw
- 45 A
- Surge current
- 90 A
Terminal map
Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.
+
positive · input
−
negative · input
Sources and sizing method
Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.
Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.