Phoenix 24/3000 Smart

Victron Phoenix 24/3000 wiring diagram

24 V Smart inverter with 230 V AC output, 2400 W continuous at 25°C. Input range 18.6–34 V; a 12 V supply is below its operating range. Requires external DC protection, protective earth and coordinated AC source selection. Nominal full-load draw is about 106 A.

Compatible systems
24 V
Rated power
2,400 W
Continuous draw
106 A

Wiring diagram

How the Phoenix 24/3000 is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Victron Phoenix 24/3000 wiring example with 3 components: House bank, Battery disconnect, Phoenix 24/3000. 3 cable connections. Crossings are not junctions.Battery disconnect B to Phoenix 24/3000 DC +: 35 mm² · 200 A fuse, 3 m one way. House bank − to Phoenix 24/3000 DC −: 25 mm², 3 m one way. House bank + to Battery disconnect A: 35 mm² · 200 A fuse, 30 cm one wayBattery disconnect B to Phoenix 24/3000 DC +: 35 mm² · 200 A fuse, 3 m one wayHouse bank − to Phoenix 24/3000 DC −: 25 mm², 3 m one wayHouse bank + to Battery disconnect A: 35 mm² · 200 A fuse, 30 cm one way24 V 200 Ah house bank. Placeholder house bank. Discharge capability of 266 A is an explicit example assumption; verify the actual continuous, surge and cranking capability and the disconnect's ratings.House bank++−−Main Battery SwitchBattery disconnectABVictron Phoenix 24/3000Phoenix 24/3000DC +DC +DC −DC −35 mm² · 200 A fuse25 mm²35 mm² · 200 A fuse
Victron Phoenix 24/3000 wiring example with 3 components: House bank, Battery disconnect, Phoenix 24/3000. 3 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Wire sizes and fuse ratings are example values; use the equipment instructions and actual installation lengths.
Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

3 m one way

24 V system

Wire
35 mm² · 2 AWG
Example fuse
200 A
Design current
106 A
Voltage drop
1.6%

Sized against ABYC E-11. The design current is the part's continuous draw. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

Show sizes in AWG

Supporting parts

  1. 6.1 m total of 35 mm² (2 AWG) marine cable
  2. Terminations for 35 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 200 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. 02 — 03/2024), checked 2026-10-01. Manufacturer documentation →

Match the DC voltage and AC version

This entry covers the 24/3000 Smart, 230 V AC inverter. Confirm that label before connecting a battery. The manufacturer datasheet specifies 18.6–34 V DC input. A 12 V supply is below its input range; that is undervoltage, not destructive overvoltage. Correct voltage does not excuse reversed polarity, which the manual warns will damage the inverter.

Provide external DC protection

Manual section 3.2.1, printed page 5, calls for 250 A external protection and 50 mm² battery cables in its 0–5 m column. Its 5–10 m column specifies two 50 mm² cables, with a footnote requiring an individual cable to carry the fuse current without overheating. Have the actual route, insulation, installation method and fault protection checked; the table is not permission to halve a cable's required ampacity.

There is no internal safety fuse. The same table recommends a 200–700 Ah bank; lithium selection also needs adequate BMS discharge and starting-current capability. Battery terminal torque must not exceed 11 Nm.

Include AC earth and source selection

The physical unit has AC L, N and PE plus a chassis ground connection. The simplified canvas omits PE, the remote connector and alarm relay. Complete those connections in the installation drawing. The manual describes a factory neutral-to-chassis link; its floating-output appendix warns that an RCD will not operate correctly without the required return path. Have the neutral bond, protective earth, RCD and any source-transfer arrangement designed together. Do not join its AC output directly to shore or generator power.

Configure shutdown and realistic loads

Use VictronConnect to set voltage, frequency, low-voltage shutdown/restart and ECO sensitivity, then test the intended appliance starts. A compatible BMS can control the remote H/L input; turning off by Bluetooth is not electrical isolation for servicing.

The catalog's approximately 106 A represents full-load planning at nominal battery voltage. Actual current rises as voltage falls. Continuous output is 2400 W at 25°C, derating to 2200 W at 40°C. The manual labels its 6000 peak as VA while the datasheet labels it W; neither is an unlimited running allowance. Verify difficult motor starts and battery sag in the installed system.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

24 V Smart inverter with 230 V AC output, 2400 W continuous at 25°C. Input range 18.6–34 V; a 12 V supply is below its operating range. Requires external DC protection, protective earth and coordinated AC source selection. Nominal full-load draw is about 106 A.

Compatible systems
24 V
Rated power
2,400 W
Continuous draw
106 A
Surge current
266 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

DC +

positive · input

200 A

DC −

negative · input

200 A

AC L

neutral · output

16 A

AC N

neutral · output

16 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. Results use the example current and run length shown above. Set your actual equipment, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with Phoenix 24/3000.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Start drawing, sizing and checking without an account. Your drawing saves in this browser. See Pricing for the equipment allowance and the one-time export offer available to you.