RNG-BATT-AGM12-100

Renogy 100Ah AGM Deep Cycle wiring diagram

12 V, 100 Ah AGM, rated at the 10-hour rate in manual A0. 30 A maximum continuous charge and 100 A continuous discharge. Requires an AGM charging profile and external circuit protection.

Nominal voltage
12 V
Capacity
100 Ah
Maximum discharge
100 A

Wiring diagram

How the 100Ah AGM is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Renogy 100Ah AGM Deep Cycle wiring example with 4 components: 100Ah AGM, Battery disconnect, Fused DC distribution, DC fridge. 5 cable connections. Crossings are not junctions.Fused DC distribution 1 to DC fridge +: 4 mm² · 15 A fuse, 3 m one way. Fused DC distribution 1 to DC fridge −: 4 mm², 3 m one way. 100Ah AGM + to Battery disconnect A: 6 mm² · 15 A fuse, 3 m one way. Battery disconnect B to Fused DC distribution IN +: 6 mm² · 15 A fuse, 3 m one way. 100Ah AGM − to Fused DC distribution IN −: 6 mm², 3 m one wayFused DC distribution 1 to DC fridge +: 4 mm² · 15 A fuse, 3 m one wayFused DC distribution 1 to DC fridge −: 4 mm², 3 m one way100Ah AGM + to Battery disconnect A: 6 mm² · 15 A fuse, 3 m one wayBattery disconnect B to Fused DC distribution IN +: 6 mm² · 15 A fuse, 3 m one way100Ah AGM − to Fused DC distribution IN −: 6 mm², 3 m one wayRenogy 100Ah AGM Deep Cycle100Ah AGM++−−Main Battery SwitchBattery disconnectABBlue Sea 5025 ST Blade Fuse BlockFused DC distributionIN +IN +IN −IN −1111Dometic CRX-65 Fridge. This 12 V example uses Dometic's 15 A supply protection and a short 1 m run with 6 mm² cable. Check the manual's voltage-specific cable graph for your route. At 24 V, the specified protection is 7.5 A. Running current and the fuse rating describe different things.DC fridge++−−4 mm² · 15 A fuse4 mm²6 mm² · 15 A fuse6 mm² · 15 A fuse
Renogy 100Ah AGM Deep Cycle wiring example with 4 components: 100Ah AGM, Battery disconnect, Fused DC distribution, DC fridge. 5 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Wire sizes and fuse ratings are example values; use the equipment instructions and actual installation lengths.
Edit this wiring example

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

Cable sizes depend on the connected equipment, current and cable lengths. Add those details in Crimp to size each run.

View diagram in AWG

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. A0 — August 15, 2025), checked 2026-10-01. Manufacturer documentation →

Identify the 100 Ah AGM battery

This is RNG-BATT-AGM12-100, a 12 V, 100 Ah sealed lead-acid AGM battery. The shared 100/200 Ah manual has separate model columns; use the 100 Ah column. AGM batteries require an AGM charging profile and ventilation. They do not acquire lithium-style BMS disconnect protection merely because a catalog component has current limits.

Use the correct current ratings

Renogy's specification table, printed pages 9–10, specifies 30 A maximum continuous charging and 100 A maximum continuous discharge. The catalog's discharge value has been corrected from 30 A to 100 A; the lower number belonged to charging. The table's 1100 A for five seconds is a short surge figure and cannot be used as a continuous load or cable rating.

This manual rates the 100 Ah model over 10 hours to 10.5 V; the 200 Ah column uses a different, 20-hour rate. Large inverter loads shorten usable runtime more than a simple amp-hour division predicts. Crimp's terminal envelope is a planning value, not a separately verified physical terminal rating.

Connect and mount the battery

The installation instructions, printed pages 4–5, specify a clean, cool, dry mounting location with airflow, M8 × 1.25 × 15 mm bolts, and direct lug-to-terminal contact. The reviewed manual does not provide a clear tightening torque; obtain the value for the actual battery hardware rather than borrowing a lithium-model torque.

Secure the battery against movement, shield the positive terminal, and provide correctly rated battery-side protection and a disconnect. The internal safety valves may release gas under fault or overcharge conditions, so a sealed battery still needs a ventilated enclosure. Charging is specified at 0–50°C, discharge at −20–60°C.

Configure the charging stages

At 25°C, the charging table, printed page 13, gives 14.4–14.8 V boost for two to four hours, with −24 mV/°C compensation, and 13.5–13.8 V float, with −18 mV/°C compensation. Match temperature sensing and compensation to the bank voltage and charger implementation.

The document contains inconsistent generic text about lithium-style cell balancing. Do not use that passage to infer an internal BMS or select a lithium profile. Its equalization table stays within 14.4–14.8 V; it does not authorize a charger's arbitrary high-voltage flooded-battery desulfation mode.

Assemble a matched bank

The manual lists four batteries maximum in a pure series bank or four in a pure parallel bank, plus separate combined examples. Use matching batteries, charge each before assembly and balance current paths. Select protection for each parallel branch and the common feed from the real cable and load design; do not assume every combination of the separate maxima is approved. See bank table, printed page 7.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

12 V, 100 Ah AGM, rated at the 10-hour rate in manual A0. 30 A maximum continuous charge and 100 A continuous discharge. Requires an AGM charging profile and external circuit protection.

Nominal voltage
12 V
Capacity
100 Ah
Maximum discharge
100 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

+

positive · bidi

150 A

−

negative · bidi

150 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Wire sizes and fuse ratings apply to the connected example, not a fixed cable size for this component. Set your actual equipment, current, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with 100Ah AGM.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.

Start drawing, sizing and checking without an account. Your drawing saves in this browser. See Pricing for the equipment allowance and the one-time export offer available to you.