RBT12300LFPSH

Renogy Core 300 Ah wiring diagram

Plan the main connections for the Renogy Core 300 Ah self-heating battery, model RBT12300LFPSH. Check its 200 A continuous limit, charger settings and heating requirements before adding your loads.

Nominal voltage
12.8 V
Capacity
300 Ah
Maximum discharge
200 A

Connection essentials

  • Protect the positive

    Use external cable protection. The battery BMS does not choose the fuse for your wiring.

  • Separate Ah from amps

    300 Ah is capacity. 200 A is the continuous current limit; size the bank cables for your actual system.

  • Heating needs charge

    Self-heating needs stable charge current greater than 10 A per battery. Intermittent solar may be insufficient.

Wiring diagram

How the 300Ah LFP is wired.

This small-load example shows the battery, disconnect and distribution path. Add your actual loads before using its cable sizes for a complete bank.

Renogy Core 300Ah Self-Heating LiFePO4 wiring example with 4 components: 300Ah LFP, Battery disconnect, Fused DC distribution, DC fridge. 5 cable connections. Crossings are not junctions.Fused DC distribution 1 to DC fridge +: 4 mm² · 15 A fuse, 3 m one way. Fused DC distribution 1 to DC fridge −: 4 mm², 3 m one way. 300Ah LFP + to Battery disconnect A: 4 mm² · 15 A fuse, 3 m one way. Battery disconnect B to Fused DC distribution IN +: 4 mm² · 15 A fuse, 3 m one way. 300Ah LFP − to Fused DC distribution IN −: 4 mm², 3 m one wayFused DC distribution 1 to DC fridge +: 4 mm² · 15 A fuse, 3 m one wayFused DC distribution 1 to DC fridge −: 4 mm², 3 m one way300Ah LFP + to Battery disconnect A: 4 mm² · 15 A fuse, 3 m one wayBattery disconnect B to Fused DC distribution IN +: 4 mm² · 15 A fuse, 3 m one way300Ah LFP − to Fused DC distribution IN −: 4 mm², 3 m one wayRenogy Core 300Ah Self-Heating LiFePO4300Ah LFP++−−Main Battery SwitchBattery disconnectABBlue Sea 5025 ST Blade Fuse BlockFused DC distributionIN +IN +IN −IN −1111Dometic CRX-65 Fridge. This 12 V example uses Dometic's 15 A supply protection and a short 1 m run with 6 mm² cable. Check the manual's voltage-specific cable graph for your route. At 24 V, the specified protection is 7.5 A. Running current and the fuse rating describe different things.DC fridge++−−4 mm² · 15 A fuse4 mm²4 mm² · 15 A fuse4 mm² · 15 A fuse
Renogy Core 300Ah Self-Heating LiFePO4 wiring example with 4 components: 300Ah LFP, Battery disconnect, Fused DC distribution, DC fridge. 5 cable connections. Crossings are not junctions.Red = positive · dark = return · dashed = signal. Wire sizes and fuse ratings are example values; use the equipment instructions and actual installation lengths.
Edit this wiring example

Size the battery cables for your loads

This example supplies a small DC load. Its cable sizes are not a full-current battery or inverter installation.

The 300 Ah capacity does not select a fuse. Size each circuit for its connected load, cable route and the battery’s current limits.

View diagram in AWG

Installation notes

Before you install.

Open a question for model-specific guidance and sources.

Verified against the manufacturer's documentation (rev. B0 — December 10, 2024), checked 2026-10-01. Manufacturer documentation →

Is this the Renogy Core battery I have?

This page covers the Core 12.8 V 300 Ah self-heating battery, RBT12300LFPSH. Check that identifier on your unit; Core Mini and REGO 300 Ah models have different instructions. See Renogy's model directory and the B0 manual.

Is 300 Ah the amount of current I can draw?

No. 300 Ah is capacity; the continuous current limit is 200 A. The specifications allow 200 A continuous charge/discharge and 390 A discharge for five seconds. The 350 A terminal planning allowance shown in Crimp is not the battery's continuous rating.

The example supplies a small DC load through a disconnect and distribution. Its cable sizes are for that example, not a full-current battery or inverter installation. Add your actual loads and chargers before sizing the bank connections.

What charger settings should I use?

Renogy specifies 14.4 V charging, recommends 150 A, and permits up to 200 A. Match the complete profile to the charging settings table. The BMS's protective cutoff is not a normal discharge target.

Will the self-heating work from a small solar array?

It needs stable charging current greater than 10 A per battery. Heating starts below 0°C and stops above 15°C. Intermittent solar may not sustain heating, especially for a parallel bank. The −20°C charging-environment rating depends on working heating; cold-charge protection otherwise applies. See the heater and protection table.

How do I attach cables and combine batteries?

Use M8 × 1.25 × 15 mm bolts at 10–12 Nm, with lugs against the terminals and washers above. Provide external cable protection; the BMS does not choose the branch fuse.

Use matching batteries and equal-length interconnects. Fully charge each battery, verify less than 0.1 V difference, and follow the balancing and bank-connection procedure.

The specification supports 4S4P. Installation text also mentions eight in parallel; confirm that conflicting larger configuration with Renogy before using it.

Technical reference

Specifications and terminal map.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Core 12.8V 300Ah self-heating LiFePO4 with internal BMS. 200A continuous discharge and 150A recommended charging; heating needs more than 10A stable charge current per battery.

Nominal voltage
12.8 V
Capacity
300 Ah
Maximum discharge
200 A

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

+

positive · bidi

350 A

−

negative · bidi

350 A
Sources and sizing method

Equipment specifications. Model details, ratings and terminal roles come from the catalog. Check your unit’s label and current manufacturer documentation for its exact revision.

Example sizing. Wire sizes and fuse ratings apply to the connected example, not a fixed cable size for this component. Set your actual equipment, current, lengths and installation conditions in Crimp before choosing hardware.

Read how the sizing works

Next step

Plan your installation with 300Ah LFP.

Open this example as a new project, or add this component to your existing diagram. Use your equipment and cable lengths to review the sizing.