Orion 24/12-70 (840W)

Victron Orion 24/12-70 wiring diagram

See the Victron Orion 24/12-70 connection points and wiring example. Open the diagram in Crimp to add your equipment and plan the cables between them.

Open this example as a new project. Use your own parts and cable lengths to make the plan yours.

Cable sizing for this example

Use the diagram as a starting point for your installation. Replace the example equipment and cable lengths with your own, and check the connections against your exact model's instructions.

3 m one way

12 V system

Wire
25 mm² · 4 AWG
Example fuse
100 A
Design current
70 A
Voltage drop
2.5%

Sized against ABYC E-11. The design current is the unit's rated output. The length is one way; voltage drop includes an equal-length return.

Run-length and manufacturer assumptions

The editable example uses 3.048 m (10 ft) runs unless a shorter run is stated. Metric overviews round these to 3 m. Adapt the parts and lengths to your installation before choosing cable and protection.

Show sizes in AWG

Wiring diagram

How the Orion 24/12-70 is wired.

Open this example in Crimp to use your own parts and cable lengths. Review the assumptions and installation notes as you adapt the circuit.

Victron Orion 24/12-70 wiring diagram, 25 mm² (4 AWG) positive feed protected by a 100 A fuse and a matching negative return between the 12 V battery bank and the unit, plus IN +, IN −.
Edit this wiring example

Build it out

Connect it to the rest of your system.

Add Orion 24/12-70 (840W) to your diagram, then connect your batteries, chargers and loads. Crimp calculates cable sizes and checks the connections as you draw.

Every cable you draw there is sized against ABYC E-11, from the same tables as the reference on this page.

Technical reference

Specifications, terminals and supporting parts.

Check the model, ratings and connection points against your own unit before choosing installation hardware.

Catalog specification

Compatible systems
12 V / 24 V
Rated output
70 A

Supporting parts

  1. 6 m total of 25 mm² (4 AWG) marine cable
  2. Terminations for 25 mm² cable, matched to the equipment's screw terminals, leads or studs
  3. 100 A fuse and holder on the positive run
  4. Heat-shrink, strain relief and terminal boots sized to the cable

Check stud sizes, fuse type, run length and how warm the space gets against the gear you actually have before you order.

Terminal map

Catalog connection points, current direction and planning limits. Check the manufacturer's pinout and connector ratings before installation.

IN +

in-pos

positive · input

50 A

IN −

in-neg

negative · input

50 A

OUT +

out-pos

positive · output

85 A

OUT −

out-neg

negative · output

85 A

Method & provenance

Where the specifications and sizing come from.

Manufacturer specifications describe the equipment. Crimp calculates cable results from the circuit and assumptions you enter.

From the maker

What the catalog says

Manufacturer, model, ratings and which terminal does what come from the catalog. A newer revision, or the nameplate on the unit in your hand, can say something different — when it does, the nameplate wins.

ABYC E-11

What Crimp worked out

Sized against ABYC E-11. Boats built to UK or EU rules answer to ISO 13297 — check these figures against it before you build. The run length and the current above are what drive the result. Crimp doesn't know how warm your space gets; draw the cable inside an engine-bay zone on the canvas and it sizes for the heat.

Read how the sizing works

Next step

Plan your installation with Orion 24/12-70.

Open this example as a new project. Add your equipment and cable lengths, then review the sizing and checks for your setup.